Cookies de la web de Omega
Utilizamos cookies en la web. Estas cookies son esenciales para que la web que funcione correctamente. Si sigue sin cambiar la configuración, vamos a suponer que usted está dispuesto a recibir todas las cookies de este sitio web.

Para obtener más información acerca de las cookies, por favor haga clic aquí
Cerrar
Cesta  |  Contacto  | 
En España 800 900 532
Fuera de España(+34) 911 776 121
Layer N Banner

Ultrasonic Non-Contact Level Measurement - Discontinued

LVU41 and LVU42 Series

Ultrasonic Non-Contact Level Measurement | LVU41 and LVU42 Series

Ultrasonic Non-Contact Level Measurement

CE
  • Available with RS232 or RS485 Communications
  • Programmable
  • Push-Button Calibration
  • Elimination of Unwanted Echoes
  • Temperature Compensated
  • Field/Bench Calibration
  • Self-Cleaning Sensor Face
  • Non-Volatile Memory (Batteries not Required)

Descripción

The LVU40 is being replaced by the LVU700.

The LVU40 series ultrasonic transmitters are advanced ultrasonic level measurement sensors for liquids. These products continue to meet demanding applications.
The microprocessor-based circuits provide a temperaturecompensated signal for improved accuracy. All models have the ability to filter false echoes produced by peripheral obstructions.
Continuous level measurement can be provided in a range of 0.3 to 18.3 m (1.0 to 60') with several power and programmability options. Point level can also be obtained using a PLC (Industrial Programmable Controller) or one of OMEGA’s CNI process controllers.

SPECIFICATIONS
Accuracy: ±0.25% of max range (in air)
Range: 0.3 to 18.3 m (1 to 60')
Resolution: 6.9 mm (0.270")
Frequency: 45 kHz
Dead Zone Range: 0.3 m (1')
Operating Temperature Range: -40 to 60°C (-40 to 140°F)
Pressure: 1 bar (15 psig max)
Mounting: 3 NPT
Beam Angle: 6 to 12° at -3 dB (model dependent)
Loss of Echo Hold: 30 seconds, 22 mA output
Power Options:
AC: 115 Vac, 60 Hz or 230 Vac, 50 Hz (±20%) 1.7 VA
DC: 12 to 30 Vdc @ 0.07 A, @ 24 Vdc R load = (Vs – 6)/24 mA
Output: 4 to 20 mA or 20 to 4 mA, 6.1 µA resolution; 750 Ω (isolated on 4-wire models only)
Optional: RS232 or RS485 communications port
Fuse: 0.125 A/250 V type
Temperature Compensation: Onboard the sensor
Calibration: Pushbutton or optional programmable
Diagnostics (Echo Profile): Via optional programmable port
Approval: Entela, CE
Conduit Entry: ½ NPT hole (PVC only)
Enclosure: Aluminum with PVC antenna ingress protection [NEMA 4X (IP66)]
Housing Dimensions: 101.6 x 226.1 m (4 x 8.9")
Sensor Diameter: 76.2 mm (3")
Realizar Pedido(Especifique el número de modelo)
Número de pieza/Desc.
Cant.
Descripción
Measurement Range 0.3 to 18.3 m (1 to 60')
LVU41-RS232
Consult Sales  
Stock: 
 
 
Three-wire 12 to 30Vdc ultrasonic with RS232 communications and Windows software
LVU41-RS485
Consult Sales  
Stock: 
 
 
Three-wire 12 to 30Vdc ultrasonic with RS485 communications and Windows software
Accessories
DPI32
€244.82
Stock: 2 semanas
 
1/32 DIN panel meter
CNI3233
€333.20
Stock: 3 semanas
 
1/32 DIN controller with relays
PSR-24S
Consult Sales  
Stock: 
 
 
Regulated power supply, US plug, 90-264 Vac input, 24 Vdc output, 400 mA, screw terminals, UL
Todos los precios se muestran en EUR
Notas: Comes complete with software and operator’s manual.
Ordering Example: (1) CNI3233 1/32 DIN controller with relays, €333.20 